Windows Server 2008 Hyper-V, Windows Server 2008 Server Core Installation Notes
|
|
- Line Tollefsen
- 5 år siden
- Visninger:
Transkript
1 Windows Server 2008 Hyper-V, Hyper-V Server 2008, and Windows Server 2008 Server Core Installation Notes Installing Dell UPS Management Software on a Hypervisor-Based Server Environment w w w. d e l l. c o m s u p p o r t. d e l l. c o m
2 Notes NOTE: A NOTE indicates important information that helps you make better use of your software. Information in this document is subject to change without notice Dell Inc. All rights reserved. Reproduction in any manner whatsoever without the written permission of Dell Inc. is strictly forbidden. Trademarks used in this text: Dell and the DELL logo are trademarks of Dell Inc.; Hyper V is a trademark, and Microsoft, Windows, and Windows Server are registered trademarks of Microsoft Corporation. Other trademarks and trade names may be used in this document to refer to either the entities claiming the marks and names or their products. Dell Inc. disclaims any proprietary interest in trademarks and trade names other than its own. April
3 Table of Contents 1 Introduction 2 Software Installation on Windows Server 2008 with Hyper-V Installing the Software Configuring UPS Shutdown Configuring Guest Operating System Shutdown on the Client-Side Software Installation on Hyper-V Server 2008 Installing the Software Configuring UPS Shutdown on a Local Agent Configuring UPS Shutdown from a Remote Machine Uninstalling the Software Configuring Guest Operating System Shutdown on the Client-Side Software Installation on Windows Server 2008 Server Core Preparing Server Core for Software Installation Installing the Software Configuring UPS Shutdown on a Local Agent Configuring the UPS from a Remote Machine Uninstalling the Software Table of Contents 3
4 1 Introduction These installation notes provide instructions for installing Dell UPS Management Software on the following hypervisor-based server environments: Microsoft Windows Server 2008 Standard x64 Edition (includes Hyper V) Microsoft Windows Server 2008 (includes Hyper V) Microsoft Hyper V Server 2008 Microsoft Hyper V Server 2008 R2 Microsoft Windows Server 2008 Server Core Microsoft Windows Server 2008 R2 Server Core 4 Introduction
5 Software Installation on Windows Server 2008 with Hyper-V This chapter provides the procedures for installing the Dell UPS Management Software on a computer that is running Microsoft Windows Server 2008 with Hyper-V. This chapter also includes instructions for starting the Dell UPS Management Software and modifying settings in the Windows Server 2008 Hyper-V environment. Installing the Software To install and start the software on Hyper-V: 1 Download the software from the Dell Web site (support.dell.com) or from the CD (F618R A04 or higher) provided with the UPS. 2 Locate the setup.exe installation file on your machine. 3 Double-click the setup.exe icon to start the installation program. 2 4 Refer to the installation and configuration manual for the Dell UPS Management Software, which provides instructions to complete the installation in a graphical user interface (GUI) environment. 5 Start the Monitor. Right click the Dell UPS Management Software Tray Icon and select Start Monitor (see Figure 1). The Dell UPS Management Software user interface window opens. Figure 1. Start Monitor Software Installation on Windows Server 2008 with Hyper-V 5
6 Configuring UPS Shutdown To select the UPS and set the shutdown parameters: 1 Select Auto Search UPS from the System menu to search for the UPS. 2 Select the desired UPS from the list of available UPSs. 3 Select Shutdown Parameters from the UPS menu to view or change the shutdown settings (see Figure 2). Figure 2. Shutdown Settings Window 6 Software Installation on Windows Server 2008 with Hyper-V
7 Configuring Guest Operating System Shutdown on the Client-Side To configure the guest operating system shutdown: 1 Start the Hyper V Manager. 2 Select one of the guest operating systems from the Virtual Machines list. Figure 3 shows an example with Windows Server 2003 and Windows Server 2008 installed as guest operating systems. 3 Select Setting from the Actions pane on the right. The server settings window opens. Figure 3. Server Settings Window 4 Select Automatic Stop Action Save from the Management list to display shutdown options (see Figure 3). Software Installation on Windows Server 2008 with Hyper-V 7
8 Select one of three ways to protect the guest operating system from an uncontrolled host machine shutdown: Save the virtual machine state. Select this option to retain the guest operating system state before the host computer shuts down. Turn off the virtual machine. Select this option to immediately turn off the virtual machine. Shut down the guest operating system. Select this option to shut down the guest operating system safely before host host machine shuts down. NOTE: The option, Shut down the guest operating system, requires that Integration Services be installed and enabled on the virtual machine. Integration Services controls the guest operating system shut down. To install Integration Services: 1 Select Insert Integration Services Setup Disk from the Action menu. 2 Click Next to complete the installation. Figure 4. Installing Integration Services 8 Software Installation on Windows Server 2008 with Hyper-V
9 Software Installation on Hyper-V Server 2008 This chapter provides the procedures for installing the Dell UPS Management Software on a computer that is running Microsoft Hyper-V Server Instructions are also provided for starting the software and modifying settings in the Hyper-V Server 2008 environment. Installing the Software To install the software on the Hyper-V Server: NOTE: You can start the installation from the CD (F618R A04 or higher) provided with the UPS, or you can download the software from the Dell Web site (support.dell.com). 1 To install the software from the CD, continue to Step 2. To install the software from the Console window proceed to Step 5. 2 Run setup.exe from the CD drive: \Windows directory. The installation interface window opens (see Figure 5). 3 Click next to complete the installation. 4 Proceed to Step 7. 3 Software Installation on Hyper-V Server
10 Figure 5. Installation Interface Window 5 To start the installation from the Console window: Download the setup.exe file to your machine from the Dell Web site (support.dell.com) or copy it from the CD. Go to the the path where the install file exists. 6 Choose standard or silent installation as follows: For standard installation, enter the command: setup The installation interface window opens (see Figure 5). Click next to complete the installation. For silent installation, enter the command: setup i silent. The software begins a silent install with no display messages or windows. Allow a few moments for installation to complete. 10 Software Installation on Hyper-V Server 2008
11 7 Confirm that the installation is successful: Enter the installation path. The default path is: c:\program file (X86)\Dell\UPSManagementSoftware Enter the command: type UPSEVENT.CSV The response confirms that the Agent is running (see Figure 6). Figure 6. Agent Started Confirmation Software Installation on Hyper-V Server
12 8 To confirm that the software is running normally, enter the following command: tasklist The task manager displays (see highlighted items in Figure 7). Figure 7. Task Manager 9 To start the software: Go to the installation path. The default path is: c:\program file (X86)\Dell\UPSManagementSoftware Enter the command: Manager The Dell UPS Management Software main window opens (see Figure 8). 12 Software Installation on Hyper-V Server 2008
13 Figure 8. Dell UPS Management Software Window Software Installation on Hyper-V Server
14 Configuring UPS Shutdown on a Local Agent To select the UPS and set the shutdown parameters: 1 Select Auto Search UPS from the System menu to search for the UPS. 2 Select the desired UPS from the list of available UPSs. 3 Select Shutdown Parameter from the UPS menu to view or change the shutdown settings (see Figure 9). Figure 9. Shutdown Settings Window 14 Software Installation on Hyper-V Server 2008
15 Configuring UPS Shutdown from a Remote Machine After the installation, you can verify and modify the shutdown settings of the Agent through a remote PC with a graphical user interface (GUI). Open the Shutdown Settings window (see Figure 10) to view settings. NOTE: If the Agent is running normally, but does not appear in the the remote computer local area network (LAN), disable the firewall, using the netsh firewall set opmode disable command. In this example, the settings Begin Shutdown Immediately if Battery Low, System and Shutdown are enabled, which means the server is protected by the software. If the AC fails, or if the battery is low, the system shuts down. Figure 10. Shutdown Settings Window Software Installation on Hyper-V Server
16 Uninstalling the Software To uninstall the software from the Hyper-V Server: 1 Go to the installation path. The default path is: c:\program file (X86)\Dell\UPSManagementSoftware 2 Enter the command: ExitAll 3 Enter the following command to display the task list: tasklist 4 If the javaw.exe process is running, enter the following command to stop it: tskill PID 5 Go to the next path: c:\program file (X86)\Dell\UPSManagementSoftware\UninstallerData 6 The command to uninstall the software depends the command used to install the software. Enter the appropriate command (see Table 1). Table 1. Uninstall Software If... then... and... The software was installed with the setup command (standard installation) The software was installed with the setup -i silent command (silent installation) enter Uninstall [the Uninstall Dell UPS Management Software window opens (see Figure 11)] enter Uninstall -i silent (the software uninstalls with no display messages or windows) follow the prompts to remove the software. 16 Software Installation on Hyper-V Server 2008
17 Figure 11. Uninstall Dell UPS Management Software Window Software Installation on Hyper-V Server
18 Configuring Guest Operating System Shutdown on the Client-Side To configure the guest operating system shutdown: 1 Start the Hyper V Manager on the client side. 2 Select one of the guest operating systems from the Virtual Machines list. Figure 12 shows an example with Windows Server 2003 and Windows Server 2008 installed as guest operating systems. 3 Select Settings from the Actions pane on the right. The server settings window opens. Figure 12. Server Settings Window 18 Software Installation on Hyper-V Server 2008
19 4 Select Automatic Stop Action Save from the Management list. 5 Select one of three ways to protect the guest operating system from an unexpected host machine shutdown: Save the virtual machine state. Select this option to retain the guest operating system state before the host computer shuts down. Turn off the virtual machine. Select this option to immediately turn off the virtual machine. Shut down the guest operating system. Select this option to shut down the guest operating system safely before host host machine shuts down. NOTE: The option, Shut down the guest operating system, requires that Integration Services be installed and enabled on the virtual machine. Integration Services controls the guest operating system shut down. To install Integration Services: 1 Select Insert Integration Services Setup Disk from the Action menu. 2 Click Next to complete the installation. Figure 13. Installing Integration Services Software Installation on Hyper-V Server
20 Software Installation on Windows Server 2008 Server Core This chapter provides the procedures for installing the Dell UPS Management Software on Windows Server 2008 Server Core. NOTE: Server Core is a minimal server installation option for computers running on the Windows Server 2008 operating system. This chapter also includes instructions for starting the Dell UPS Management Software and modifying settings in the Server Core environment. Preparing Server Core for Software Installation Before installing the software on Server Core, modify the network and port settings. To modify settings: 1 Shutdown the firewall, using the command: netsh firewall set opmode disable 2 Enable the remote desktop function: 4 Open the Registry Editor (see Figure 14), using the command: Regedit 20 Software Installation on Windows Server 2008 Server Core
21 Figure 14. Registry Editor Edit HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Control\Terminal Server\fDenyTSConnections = 0. Open the port, using the command: Netsh firewall set portopening tcp 3389 Software Installation on Windows Server 2008 Server Core 21
22 Installing the Software To install the software on Server Core: NOTE: You can start the installation from the CD (F618R A04 or higher) provided with the UPS, or you can download the software from the Dell Web site (support.dell.com). 1 To install the software from the CD, continue to Step 2. To install the software from the Console window proceed to Step 5. 2 Run setup.exe from the CD drive: \Windows directory. The installation interface window opens (see Figure 15). 3 Click next to complete the installation. 4 Proceed to Step 7. Figure 15. Installation Interface Window 5 To start the installation from the Console window: Download the setup.exe file to your machine from the Dell Web site (support.dell.com) or copy it from the CD. Go the path where the installation file exists. 22 Software Installation on Windows Server 2008 Server Core
23 6 Choose standard or silent installation as follows: For standard installation, enter the command: setup The installation interface window opens (see Figure 15). Click next to complete the installation. For silent installation, enter the command: setup i silent The software begins a silent install with no display messages or windows. Allow a few moments for installation to complete. 7 Confirm that the installation is successful: Enter the installation path. The default path is: c:\program file (X86)\Dell\UPSManagementSoftware Enter the command: type UPSEVENT.CSV The response confirms that the Agent is running (see Figure 16). Figure 16. Agent Started Confirmation 8 To start the Dell UPS Management Software: Go to the installation path. The default path is: c:\program file (X86)\Dell\UPSManagementSoftware Enter the command: Manager The Dell UPS Management Software main window opens. Software Installation on Windows Server 2008 Server Core 23
24 9 To confirm that the software is running normally, enter the command: tasklist The task manager displays (see highlighted items in Figure 17). Figure 17. Task Manager 24 Software Installation on Windows Server 2008 Server Core
25 Configuring UPS Shutdown on a Local Agent To select the UPS and set the shutdown parameters: 1 Select Auto Search UPS from the System menu to search for the UPS. 2 Select the desired UPS from the list. 3 Select Shutdown Parameter from the UPS menu to view or change the shutdown settings (see Figure 18). Figure 18. Shutdown Settings Window Software Installation on Windows Server 2008 Server Core 25
26 Configuring the UPS from a Remote Machine After the installation, you can verify and modify the shutdown settings of the Agent through a remote PC with a graphical user interface (GUI). Open the Shutdown Settings window (see Figure 19) to view settings. NOTE: If the Agent is running normally, but does not appear in the the remote computer local area network (LAN), disable the firewall, using the netsh firewall set opmode disable command. In this example, the settings Begin Shutdown Immediately if Battery Low, System and Shutdown are enabled, which means the server is protected by the software. If the AC fails, or if the battery is low, the system shuts down. Figure 19. Shutdown Settings Window 26 Software Installation on Windows Server 2008 Server Core
27 Uninstalling the Software To uninstall the Dell UPS Management Software from the Server Core: 1 Go to the installation path. The default path is: c:\program file (X86)\Dell\UPSManagementSoftware 2 Enter the command: ExitAll 3 Enter the following command to display the task list: tasklist 4 If the javaw.exe process is running, enter the following command to stop it: tskill PID 5 Go to the next path c:\program file (X86)\Dell\UPSManagementSoftware\UninstallerData. 6 The command to uninstall the software depends the command used to install the software. Enter the appropriate command (see Table 2). Table 2. Uninstall Software If... then... and... The software was installed with the setup command (standard installation) The software was installed with the setup -i silent command (silent installation) enter Uninstall [the Uninstall Dell UPS Management Software window opens (see Figure 20)] enter Uninstall -i silent (the software uninstalls with no display messages or windows) follow the prompts to remove the software. Software Installation on Windows Server 2008 Server Core 27
28 Figure 20. Uninstall Dell UPS Management Software Window 28 Software Installation on Windows Server 2008 Server Core
GLOBALCOMSERVER HP 9100C DIGITAL SENDER GATEWAY ADMINISTRATOR S GUIDE 1998 AVM INFORMATIQUE (UPDATED: AUGUST 22, 2006)
PAGE 1 / 13 GLOBALCOMSERVER HP 9100C DIGITAL SENDER GATEWAY ADMINISTRATOR S GUIDE 1998 AVM INFORMATIQUE (UPDATED: AUGUST 22, 2006) PAGE 2 / 13 LICENSE LICENSE Information in this document is subject to
Start Here USB *CC * *CC * USB USB
1 USB Start Here USB 11 USB WARNING: To ensure that the software is installed correctly, do not connect the USB cable until step 11. 11 USB 2 a. b. Lower both the paper tray and the print cartridge door.
Trådløsnett med Windows XP. Wireless network with Windows XP
Trådløsnett med Windows XP Wireless network with Windows XP Mai 2013 Hvordan koble til trådløsnettet eduroam med Windows XP Service Pack 3? How to connect to the wireless network eduroam with Windows XP
Trådløsnett med Windows Vista. Wireless network with Windows Vista
Trådløsnett med Windows Vista Wireless network with Windows Vista Mai 2013 Hvordan koble til trådløst nettverk eduroam med Windows Vista? How to connect to the wireless networkeduroam with Windows Vista?
Trådløst nett UiT. Feilsøking. Wireless network UiT Problem solving
Trådløst nett UiT Feilsøking Wireless network UiT Problem solving April 2016 Problemer med tilkobling til trådløsnettet Eduroam kan enten løses ved å laste ned en installasjonfil fra https://cat.eduroam.org
Hybrid Cloud and Datacenter Monitoring with Operations Management Suite (OMS)
Hybrid Cloud and Datacenter Monitoring with Operations Management Suite (OMS) Varighet: 5 Days Kurskode: M10996 Version: A Opplæringsmetoder: Virtuell opplæring Beskrivelse: This five-day course will provide
Hvordan føre reiseregninger i Unit4 Business World Forfatter:
Hvordan føre reiseregninger i Unit4 Business World Forfatter: dag.syversen@unit4.com Denne e-guiden beskriver hvordan du registrerer en reiseregning med ulike typer utlegg. 1. Introduksjon 2. Åpne vinduet
Compello Fakturagodkjenning Versjon 10.5 As a Service. Tilgang til Compello Desktop - Regnskapsføring og Dokument import
Compello Fakturagodkjenning Versjon 10.5 As a Service Tilgang til Compello Desktop - Regnskapsføring og Dokument import Dokumentopplysninger 2018 Compello AS. Med enerett. Microsoft, MS-DOS og Windows
Sascha Schubert Product Manager Data Mining SAS International Copyright 2006, SAS Institute Inc. All rights reserved.
Extending SAS Enterprise Miner Sascha Schubert Product Manager Data Mining SAS International Agenda Architecture of SAS Enterprise Miner 5.2 Access to SAS Data Mining Functionality The Flexibility of the
Microsoft Dynamics C5 Version 2008 Oversigt over Microsoft Reporting Services rapporter
Reporting Services - oversigt Microsoft Dynamics C5 Version 2008 Oversigt over Microsoft Reporting Services rapporter Summary Efterfølgende vises en oversigt over de rapporter som er indeholdt i Microsoft
Compello Fakturagodkjenning Versjon 10 Software as a service. Tilgang til ny modulen Regnskapsføring
Compello Fakturagodkjenning Versjon 10 Software as a service Tilgang til ny modulen Regnskapsføring Dokumentopplysninger 2018 Compello AS. Med enerett. Microsoft, MS-DOS og Windows er registrerte varemerker
Rom-Linker Software User s Manual
Rom-Linker Software User s Manual Tel.: +886-2-2274-1347 Fax. +886-2-2273-3014 Http://www.hmt.com.tw e-mail: hmtsales@hmt.com.tw Contents Catalogue Page (1) Rom-Linker Starting Screen... 01 (2) Rom-Linker
HP LaserJet MFP. Analog Fax Accessory 300
HP LaserJet MFP Analog Fax Accessory 300 Send Fax Driver Guide Send Fax Driver Vejledning Faksinlähetysohjaimen käyttöopas Håndbok for Send faks-driveren Drivrutinsguide för att skicka fax 12234 HP LaserJet
Quantitative Spectroscopy Chapter 3 Software
Quantitative Spectroscopy Chapter 3 Software Copyright 2006 Mettler-Toledo AutoChem, Inc. 1 Chapter 3 Outline P-matrix P-matrix with automatic frequency select PLS: Choosing a region PLS: Selecting the
Unit Relational Algebra 1 1. Relational Algebra 1. Unit 3.3
Relational Algebra 1 Unit 3.3 Unit 3.3 - Relational Algebra 1 1 Relational Algebra Relational Algebra is : the formal description of how a relational database operates the mathematics which underpin SQL
Information search for the research protocol in IIC/IID
Information search for the research protocol in IIC/IID 1 Medical Library, 2013 Library services for students working with the research protocol and thesis (hovedoppgaven) Open library courses: http://www.ntnu.no/ub/fagside/medisin/medbiblkurs
SQL Server guide til e-lector
LES LETTERE, LES RASKERE, FÅ LESELYST! SQL Server guide til e-lector Innhold 1 Innledning... 2 2 SQL Express 2008 R2 installasjon... 2 3 Etter installasjon... 4 3.1 SQL Express... 4 3.1.1 Nettverksoppsett
of color printers at university); helps in learning GIS.
Making a Home Page Why a Web Page? Easier to submit labs electronically (lack of color printers at university); Easier to grade many labs; Provides additional computer experience that helps in learning
6105 Windows Server og datanett
6105 Windows Server og datanett Labøving: Deling av mapper, filer og skrivere i arbeidsgruppe Oppgavebeskrivelse Her forklares kort hva øvingen går ut på for de som ønsker å finne løsningen selv. Hvis
User Guide
User Guide Micro USB port Back up new data Restore previously backed up data More settings Enable or disable a SIM card Select 4G/3G SIM Select default SIM for data services Configure SIM
6105 Windows Server og datanett
6105 Windows Server og datanett Labøving: Deling av mapper, filer og skrivere i arbeidsgruppe Hensikt/målsetning Øvingen gir erfaring med enkel deling av mapper, filer og skrivere i en Windows arbeidsgruppe.
Trådløsnett med. Wireless network. MacOSX 10.5 Leopard. with MacOSX 10.5 Leopard
Trådløsnett med MacOSX 10.5 Leopard Wireless network with MacOSX 10.5 Leopard April 2010 Slå på Airport ved å velge symbolet for trådløst nettverk øverst til høyre på skjermen. Hvis symbolet mangler må
Vedlegg 2 Dokumentasjon fra TVM leverandør
(Step 7) Payment selection or date modification state This screen is displayed after validation of a date in the calendar screen. The customer can: - Modify again the date by pressing the Validity begin:
Trådløst nett UiT Feilsøking. Wireless network UiT Problem solving
Trådløst nett UiT Feilsøking Wireless network UiT Problem solving April 2015 Hvorfor får jeg ikke koblet meg opp mot trådløst nettverk med Windows 7? Why can t I connect to the wireless network with Windows
Slope-Intercept Formula
LESSON 7 Slope Intercept Formula LESSON 7 Slope-Intercept Formula Here are two new words that describe lines slope and intercept. The slope is given by m (a mountain has slope and starts with m), and intercept
Tilpasning av Windows 2000 server til Skolelinux tynnklienttjener
Tilpasning av Windows 2000 server til Skolelinux tynnklienttjener Bernt Johnsen, Ski videregående skole Ragnar Wisløff, LinuxLabs AS November 2004 Innholdsliste Innledning...2 Ansvarsfraskrivelse...2 Endringer
SmartPass Mini User Manual BBNORGE.NO
SmartPass Mini User Manual BBNORGE.NO Intro Welcome to the usermanual for your SmartPass Mini system. The first time you start the SmartPass you have to request a License. This is to regiser your license
1 User guide for the uioletter package
1 User guide for the uioletter package The uioletter is used almost like the standard LATEX document classes. The main differences are: The letter is placed in a \begin{letter}... \end{letter} environment;
TB-615 / TB-617 Wireless slim keyboard. EN User guide SE Användarhandledning FI Käyttöohje DK Brugervejledning NO Bruksanvisning
TB-615 / TB-617 Wireless slim keyboard EN User guide SE Användarhandledning FI Käyttöohje DK Brugervejledning NO Bruksanvisning EN User guide You have bought a wireless keyboard to use with Windows XP,
1. Installasjon av SharePoint 2013
Avdeling for informatikk og e-læring, Høgskolen i Sør-Trøndelag Installasjon av SharePoint 2013 Stein Meisingseth 02.09.2013 Lærestoffet er utviklet for faget LO205D Microsoft SharePoint 1. Installasjon
The regulation requires that everyone at NTNU shall have fire drills and fire prevention courses.
1 The law The regulation requires that everyone at NTNU shall have fire drills and fire prevention courses. 2. 3 Make your self familiar with: Evacuation routes Manual fire alarms Location of fire extinguishers
REMOVE CONTENTS FROM BOX. VERIFY ALL PARTS ARE PRESENT READ INSTRUCTIONS CAREFULLY BEFORE STARTING INSTALLATION
2011-2014 FORD EXPLORER PARTS LIST Qty Part Description Qty Part Description 1 Bull Bar 2 12mm x 35mm Bolt Plates 1 Passenger/Right Mounting Bracket 2 12mm Nut Plate 1 Driver/Left Mounting Bracket 2 12mm
HONSEL process monitoring
6 DMSD has stood for process monitoring in fastening technology for more than 25 years. HONSEL re- rivet processing back in 990. DMSD 2G has been continuously improved and optimised since this time. All
Elektronisk innlevering/electronic solution for submission:
VIKINGTIDSMUSEET Plan- og designkonkurranse/design competition Elektronisk innlevering/electronic solution for submission: Det benyttes en egen elektronisk løsning for innlevering (Byggeweb Anbud). Dette
SERVICE BULLETINE 2008-4
S e r v i c e b u l l e t i n e M a t e r i e l l Materiellsjef F/NLF kommuniserer påminnelse omkring forhold som ansees som vesentlige for å orientere om viktige materiellforhold. Målgruppen for Servicbulletinen
Norsk (English below): Guide til anbefalt måte å printe gjennom plotter (Akropolis)
Norsk (English below): Guide til anbefalt måte å printe gjennom plotter (Akropolis) 1. Gå til print i dokumentet deres (Det anbefales å bruke InDesign til forberedning for print) 2. Velg deretter print
AKENEOPIM User Guide Version 1.6. Catalog settings USER GUIDE CATALOG SETTINGS. Version 1.6. Copyright AKENEO SAS The Open Source PIM
USER GUIDE CATALOG SETTINGS CONTENTS Manage Attributes 5 View Attributes 5 Page numbering 5 The filters 6 Screening product attributes 7 Shortcut actions on each attribute 7 Create an attribute 8 Edit
Juridiske aspekter ved publisering i åpne institusjonelle arkiv
Juridiske aspekter ved publisering i åpne institusjonelle arkiv Professor dr juris Olav Torvund Publisering i åpne institusjonelle arkiv Førstegangspublisering Masteroppgaver Doktoravhandlinger (?) Grålitteratur
EN Skriving for kommunikasjon og tenkning
EN-435 1 Skriving for kommunikasjon og tenkning Oppgaver Oppgavetype Vurdering 1 EN-435 16/12-15 Introduction Flervalg Automatisk poengsum 2 EN-435 16/12-15 Task 1 Skriveoppgave Manuell poengsum 3 EN-435
Blackwire 215/225. Analogt hodesett med ledning. Brukerhåndbok
Blackwire 215/225 Analogt hodesett med ledning Brukerhåndbok Innhold Velkommen 3 Trenger du mer hjelp? 3 Hva er det i esken 4 Integrerte kontroller 5 Bruke hodesettet 6 Justere hodebøylen 6 Plassere mikrofonbøylen
Endelig ikke-røyker for Kvinner! (Norwegian Edition)
Endelig ikke-røyker for Kvinner! (Norwegian Edition) Allen Carr Click here if your download doesn"t start automatically Endelig ikke-røyker for Kvinner! (Norwegian Edition) Allen Carr Endelig ikke-røyker
EMPIC MEDICAL. Etterutdanningskurs flyleger 21. april Lars (Lasse) Holm Prosjektleder Telefon: E-post:
EMPIC MEDICAL Etterutdanningskurs flyleger 21. april 2017 Lars (Lasse) Holm Prosjektleder Telefon: +47 976 90 799 E-post: Lrh@caa.no it-vakt@caa.no Luftfartstilsynet T: +47 75 58 50 00 F: +47 75 58 50
Bestille trykk av doktoravhandling Ordering printing of PhD Thesis
Bestille trykk av doktoravhandling Ordering printing of PhD Thesis Brukermanual / User manual Skipnes Kommunikasjon ntnu.skipnes.no PhD Thesis NTNU LOG IN NOR: Gå inn på siden ntnu.skipnes-wtp.no, eller
Oversikt over SMS kommandoer for Holars 2020G
Oversikt over SMS kommandoer for Holars 2020G Det er to ulike menyer for å programmere / styre sentralen. 1. Bruker SMS Her kan brukeren styre alarmen Av/På samt styre utgangsmoduler og Waveman moduler.
Exercise 1: Phase Splitter DC Operation
Exercise 1: DC Operation When you have completed this exercise, you will be able to measure dc operating voltages and currents by using a typical transistor phase splitter circuit. You will verify your
Dell OptiPlex 790. Informasjon om konfigurasjon og funksjoner. Om advarsler. Minitårn Sett forfra og bak
Dell OptiPlex 790 Informasjon om konfigurasjon og funksjoner Om advarsler ADVARSEL: En ADVARSEL angir potensiell fare for skade på eiendom, personskade eller død. Sett forfra og bak Figur 1: Sett forfra
FBWF under Windows 7 Standard
Systemet kjører med FBWF (File Based Write Filter) som minsker skriving til disk og som også beskytter systemet for endringer. FBWF er også en god beskyttelse i tilfelle strømbrudd. FBWF funksjonen er
IBM. Advanced Settings Utility, v9.63 User's Guide
IBM Advanced Settings Utility, v9.63 User's Guide Version 9.63 IBM Advanced Settings Utility, v9.63 User's Guide Version 9.63 Note Before using this information and the product it supports, read the information
Sikkert Drillingnettverk på CAT-D Rig
Sikkert Drillingnettverk på CAT-D Rig Med fokus på IT sikkerhet i offshore bransjen Kristiansand, 21/10/2014, Asgeir Skretting, Dag Tang Sikkert Drillingnettverk på CAT-D Rig Agenda Hvorfor sikker offshore
INSTALLATION GUIDE FTR Cargo Rack Regular Ford Transit 130" Wheelbase ( Aluminum )
INSTALLATION GUIDE 1505-FTR Cargo Rack Regular Ford Transit 130" Wheelbase ( Aluminum ) QUICK START GUIDE Phase 1 - Assembly q 1.1 Setup... q 1.2 Cargo Rack Assembly... 3-4 5-6 Phase 2 - Installation q
WWW.CERT.DK. Introduction to DK- CERT Vulnerability Database
Introduction to DK- CERT Vulnerability Database By Peter Rickers and Mikael Stamm 1 Fundamental Idea Securing of networks, in-house and externally Savings for the costumers Making admission to the correct
Samlede Skrifter PDF. ==>Download: Samlede Skrifter PDF ebook
Samlede Skrifter PDF ==>Download: Samlede Skrifter PDF ebook Samlede Skrifter PDF - Are you searching for Samlede Skrifter Books? Now, you will be happy that at this time Samlede Skrifter PDF is available
Trigonometric Substitution
Trigonometric Substitution Alvin Lin Calculus II: August 06 - December 06 Trigonometric Substitution sin 4 (x) cos (x) dx When you have a product of sin and cos of different powers, you have three different
Databases 1. Extended Relational Algebra
Databases 1 Extended Relational Algebra Relational Algebra What is an Algebra? Mathematical system consisting of: Operands --- variables or values from which new values can be constructed. Operators ---
PSi Apollo. Technical Presentation
PSi Apollo Spreader Control & Mapping System Technical Presentation Part 1 System Architecture PSi Apollo System Architecture PSi Customer label On/Off switch Integral SD card reader/writer MENU key Typical
SHORE POWER CONVERTER LIST 2018
2018 POWER AT YOUR CONTROL Shore cord capacities These tables provide a approximate indication of the amount of kva capacity of different amperage shore cords at common worldwide voltages. Use these tables
IBM Tivoli Netcool Performance Manager Model Maker Document Revision R2E1. Model Maker Installation and User Guide
IBM Tivoli Netcool Performance Manager 1.3.3 Model Maker 1.3.0 Document Revision R2E1 Model Maker Installation and User Guide Note Before using this information and the product it supports, read the information
Windlass Control Panel
SIDE-POWER 86-08955 Windlass Control Panel v1.0.2 Windlass Systems Installasjon manual SLEIPNER MOTOR AS P.O. Box 519 N-1612 Fredrikstad Norway Tel: +47 69 30 00 60 Fax: +47 69 30 00 70 w w w. s i d e
SeaWalk No 1 i Skjolden
SeaWalk No 1 i Skjolden August 2011 Luster Kommune Marked I løpet av de neste 10 år er verdens cruisemarked ventet å doble seg. Veksten forventes større i Europa enn i Kariben og USA. Markedet vil lete
Innholdsfortegnelse... 1 Endringslogg UD BETALINGSTERMINAL NETS NEW DRIVERS FULL SUPPORT WINDOWS
ENDRINGSLOGG INNHOLDSFORTEGNELSE Innholdsfortegnelse... 1 Endringslogg 2017.151.1... 3 UD-17.136 BETALINGSTERMINAL NETS NEW DRIVERS FULL SUPPORT WINDOWS 10... 3 UD-17.137 UTESTÅENDE NOT SHOWIN CROSSED
SuperOffice hurtigstart guide
SuperOffice hurtigstart guide Searchdaimon ES (Enterprise Server) Innholdsfortegnelse Innlednig... 2 Instalere SuperOffice konektor... 3 Steg 2 Database driver... 4 Steg 3 Database setting... 5 Steg 4
INF2120 Tools at your fingertips
INF2120 Tools at your fingertips Version 070124 23-Jan-07 INF2120 Prosjekt i modellering 1 Eclipse og RSM en god IDE? med foiler også av Andreas Limyr og Gøran K. Olsen før begge Ifi, nå begge Sintef 23-Jan-07
Om Samba/fildeling. Hans Nordhaug Institutt for informatikk Høgskolen i Molde
Om Samba/fildeling Hans Nordhaug Institutt for informatikk Høgskolen i Molde 13.09.2016 Tema 1 Introduksjon Om SMB/CIFS Om Samba Hvorfor Samba? 2 Generelt Delte ressurser Om protokollen SMB (CIFS) SMB
Om Samba/fildeling. Hans Nordhaug 17.09.2013. Institutt for informatikk Høgskolen i Molde
Om Samba/fildeling Hans Nordhaug Institutt for informatikk Høgskolen i Molde 17.09.2013 Tema 1 Introduksjon Om SMB Om Samba Hvorfor Samba? 2 Generelt Delte ressurser Server Message Block En protokoll for
TriCOM XL / L. Energy. Endurance. Performance.
TriCOM XL / L Energy. Endurance. Performance. L and XL - the new generation Sample charging station with chargers TriCOM L / XL Innovative charging technology The new TriCOM L - XL chargers are controlled
LifeSize SDI Adapter installasjonsveiledning
LifeSize SDI Adapter installasjonsveiledning July 2007 Part Number 132-00070-001 Revision 01 Copyright Notice 2007 LifeSize Communications Inc, and its licensors. All rights reserved. LifeSize Communications
Ethernet Starter Kit II
Ethernet Starter Kit II Tel: +49 (2405) 408 550 Fax: +49 (2405) 408 554 44 Email: info@wilke.de 1 Ethernet Starter Kit II Welcome to the Ethernet Starter Kit II. This short description is intended to
Gaute Langeland September 2016
Gaute Langeland September 2016 Svak krone 10,4 10 9,6 9,2 8,8 8,4 EURNOK 8 7,6 7,2 6,8 3jan00 3jan02 3jan04 3jan06 3jan08 3jan10 3jan12 3jan14 3jan16 2 12.10.2016 Ikke helt tilfeldig 3 12.10.2016 Hvordan
Smart High-Side Power Switch BTS730
PG-DSO20 RoHS compliant (green product) AEC qualified 1 Ω Ω µ Data Sheet 1 V1.0, 2007-12-17 Data Sheet 2 V1.0, 2007-12-17 Ω µ µ Data Sheet 3 V1.0, 2007-12-17 µ µ Data Sheet 4 V1.0, 2007-12-17 Data Sheet
UNIVERSITETET I OSLO
UNIVERSITETET I OSLO Det matematisk-naturvitenskapelige fakultet Eksamen i INF 3230 Formell modellering og analyse av kommuniserende systemer Eksamensdag: 4. juni 2010 Tid for eksamen: 9.00 12.00 Oppgavesettet
Du må håndtere disse hendelsene ved å implementere funksjonene init(), changeh(), changev() og escape(), som beskrevet nedenfor.
6-13 July 2013 Brisbane, Australia Norwegian 1.0 Brisbane har blitt tatt over av store, muterte wombater, og du må lede folket i sikkerhet. Veiene i Brisbane danner et stort rutenett. Det finnes R horisontale
Server-Side Eclipse. Martin Lippert akquinet agile GmbH
Server-Side Eclipse Martin Lippert akquinet agile GmbH martin.lippert@akquinet.de 2006 by Martin Lippert, martin.lippert@akquinet.de; made available under the EPL v1.0 Outline Introduction Why Eclipse?
IBM Tivoli Netcool Performance Manager Model Maker Document Revision R2E1. Model Maker Installation and User Guide
IBM Tivoli Netcool Performance Manager Model Maker 1.2.1 Document Revision R2E1 Model Maker Installation and User Guide Note Before using this information and the product it supports, read the information
INSTALLATION GUIDE FTR Cargo Rack Regular Ford Transit 130" Wheelbase ( Aluminum )
INSTALLATION GUIDE 1505-FTR Cargo Rack Regular Ford Transit 130" Wheelbase ( Aluminum ) QUICK START GUIDE Phase 1 - Assembly q 1.1 Setup... q 1.2 Cargo Rack Assembly... 3-4 5-6 Phase 2 - Installation q
Administrasjon av postnummersystemet i Norge Post code administration in Norway. Frode Wold, Norway Post Nordic Address Forum, Iceland 5-6.
Administrasjon av postnummersystemet i Norge Frode Wold, Norway Post Nordic Address Forum, Iceland 5-6. may 2015 Postnumrene i Norge ble opprettet 18.3.1968 The postal codes in Norway was established in
CSR Harvesting Final Meeting September, 2015 Brest, France. Anne Che-Bohnenstengel & Matthias Pramme, BSH
CSR Harvesting Final Meeting 16. 17. September, 2015 Brest, France Anne Che-Bohnenstengel & Matthias Pramme, BSH Topics Introduction Harvesting Workflow CSR-Harvesting Report Monitoring portal for harvesting
Elektronisk termostat med spareprogram. Lysende LCD display øverst på ovnen for enkel betjening.
Elektronisk termostat med spareprogram. Lysende LCD display øverst på ovnen for enkel betjening. 27.5 LCD Electronic thermostat with program setting. Bright LCD display placed at the top of the heater
Emneevaluering GEOV272 V17
Emneevaluering GEOV272 V17 Studentenes evaluering av kurset Svarprosent: 36 % (5 av 14 studenter) Hvilket semester er du på? Hva er ditt kjønn? Er du...? Er du...? - Annet PhD Candidate Samsvaret mellom
Time & Attendance Timeregistrering. End User Sluttbruker
Time & Attendance Timeregistrering End User Sluttbruker Introduction Introduksjon This presentation is a step by step walkthrough of the time registration process in our HR system. The information is presented
Resesjonsrisiko? Trondheim 7. mars 2019
Resesjonsrisiko? Trondheim 7. mars 2019 Vi har sett en klar avmatning i global økonomi Source: IHS Markit, Macrobond Fincial Kina 1 men vi tror vi ser stabilisering/ny oppgang fra andre kvartal Vi tror
Server-Side Eclipse. Bernd Kolb Martin Lippert it-agile GmbH
Server-Side Eclipse Bernd Kolb b.kolb@kolbware.de Martin Lippert it-agile GmbH lippert@acm.org 2006 by Martin Lippert, lippert@acm.org; made available under the EPL v1.0 Outline Introduction Why Eclipse?
ENERGY STAR Qualified UPS Products
The ENERGY STAR Program was established by the U.S. Environmental Protection Agency (EPA) as a way to identify and promote energy-efficient products, in order to reduce energy consumption, help individuals
Ny personvernlovgivning er på vei
Ny personvernlovgivning er på vei Er du forberedt? 23. august 2017 There are lines you cannot cross. There are rules to the game. But within the lines and following the rules, you are only limited by your
Endringer i neste revisjon av EHF / Changes in the next revision of EHF 1. October 2015
Endringer i neste revisjon av / Changes in the next revision of 1. October 2015 INFORMASJON PÅ NORSK 2 INTRODUKSJON 2 ENDRINGER FOR KATALOG 1.0.3 OG PAKKSEDDEL 1.0.2 3 ENDRINGER FOR ORDRE 1.0.3 4 ENDRINGER
Passenger Terminal World Expo 2011 Copenhagen, Denmark. Steven B. Cornell Assoc. Vice President
Passenger Terminal World Expo 2011 Copenhagen, Denmark Steven B. Cornell Assoc. Vice President Overview PRT Definition Planning Parameters for Airport Projects Speed Capacity Geometrics Costs New Airport
Safering / Safeplus Retrofit of Ronis key for disconnector Interlock type EL11AP V and Sv modules
Safering / Safeplus Retrofit of Ronis key for disconnector Interlock type EL11AP V and Sv modules Installation instructions www.abb.com Document status Responsible RELEASED NODIS Location Date Name Prepared
DecisionMaker Frequent error codes (valid from version 7.x and up)
DecisionMaker Frequent error codes (valid from version 7.x and up) DM Frequent Error Codes Bisnode Credit IT 03.02.2014 1 (5) CONTENTS 1 Target... 3 2 About this document... 3 3 Error codes an messages...
Justeringsanvisninger finnes på de to siste sidene.
d Montering av popup spredere Justeringsanvisninger finnes på de to siste sidene. Link til monteringsfilm på youtube: http://youtu.be/bjamctz_kx4 Hver spreder har montert på en "svinkobling", det vil si
IBM Tivoli Netcool Performance Manager Model Maker Document Revision R2E1. Model Maker Installation and User Guide
IBM Tivoli Netcool Performance Manager Model Maker 1.2.4 Document Revision R2E1 Model Maker Installation and User Guide Note Before using this information and the product it supports, read the information
Den som gjør godt, er av Gud (Multilingual Edition)
Den som gjør godt, er av Gud (Multilingual Edition) Arne Jordly Click here if your download doesn"t start automatically Den som gjør godt, er av Gud (Multilingual Edition) Arne Jordly Den som gjør godt,
IBM Endpoint Manager. OS Deployment V3.8 User's Guide - Draft for Beta V1.1 (Do not distribute)
IBM Endpoint Manager OS Deployment V3.8 User's Guide - Draft for Beta V1.1 (Do not distribute) IBM Endpoint Manager OS Deployment V3.8 User's Guide - Draft for Beta V1.1 (Do not distribute) Note Before
IBM Tivoli Netcool Performance Manager Model Maker Document Revision R2E2. Model Maker Installation and User Guide
IBM Tivoli Netcool Performance Manager Model Maker 1.2.6 Document Revision R2E2 Model Maker Installation and User Guide Note Before using this information and the product it supports, read the information
Bærekraftig FM til tiden/ Bærekraftig FM på tid
Downloaded from orbit.dtu.dk on: Sep 28, 2019 Bærekraftig FM til tiden/ Bærekraftig FM på tid Nielsen, Susanne Balslev Publication date: 2015 Document Version Peer reviewed version Link back to DTU Orbit
User Guide. (For 6180 Industrial Computers)
User Guide (For 6180 Industrial Computers) This document describes the Keypad Configuration Utility and how it is used to create keypad configurations for the 6180 Industrial computers. For information
Brukerdokumentasjon Brukerdokumentasjon
Brukerdokumentasjon Brukerdokumentasjon 2 Brukerveiledning For en som skal ta en test: For den som skal ta en test er det mening at en bruksanvisning skal være unødvendig. De få informasjonene som en bruker
80. Lincoln to Parklands
80. Lincoln to Parklands Valid from 8 December 2014 Bus route: LincoIn University X Lincoln Township Prebbleton Westfield Riccarton X Christchurch Hospital X Central Station X Eastgate Shopping Centre
Oppgave 1a Definer følgende begreper: Nøkkel, supernøkkel og funksjonell avhengighet.
TDT445 Øving 4 Oppgave a Definer følgende begreper: Nøkkel, supernøkkel og funksjonell avhengighet. Nøkkel: Supernøkkel: Funksjonell avhengighet: Data i en database som kan unikt identifisere (et sett
IBM Tivoli Netcool Performance Manager Model Maker Document Revision R2E1. Model Maker Installation and User Guide
IBM Tivoli Netcool Performance Manager Model Maker 1.2.3 Document Revision R2E1 Model Maker Installation and User Guide Note Before using this information and the product it supports, read the information
Reliable RT processing @ Spotify
Reliable RT processing @ Spotify Pablo Barrera February 5, 2014 Spotify 3 Spotify the right music for every moment over 6 million paying customers over 24 million active users each