Ineos Norge AS Ansatte 340 Omsetning 4 milliarder Produserer årlig: 520.000 tonn VCM 260.000 tonn klor 280.000 tonn lut 7.500 tonn hydrogen 30.000 tonn saltsyre Copyright INEOS 2006
Vann - 21.000 m3/h Salt - 500.000 tonn i året Strøm - 152 MW Copyright INEOS 2006
Firewall Business Network Plant Wide Data Warehouse PHD Remote Operations Experion Station Multivariable Control and Optimization Profit Suite Casual User Secure Read Only Process Display Web Server eserver Trend Server PCC History Collector PHD Advanced Applications Network Integrated Supervisory Control ACE Engineering Station Experion Flex Station Web-based Experion Station Redundant Global Database & Historian Experion Server Primary Domain Controller PDC Supervisory Control Network Local Control Network SIL 3 Safety System Fail Safe Manager Regulatory, Logic Sequential & Model Based Controls C200 & Profit Loop SIL 3 Safety System Fail Safe Manager Process Manager Basic Controller Copyright INEOS 2006
Innføring av FF Øke produksjonen av klor dvs. fjerne import av EDC. 2 stk nye klorfabrikker Nytt Honeywell system Experion. Nye muligheter Copyright INEOS 2006
Hvorfor FF Foundation Fieldbus Prosjektet var etablert og kontrakt inngått med Uhde uten FF feltinstrumenter. Teknisk miljø overbeviste ledelsen om at det var fornuftig å satse på FF instrumentering. FF ble implementert i prosjektet for analoge inn- og ut-ganger i DCS nodene. Ingen økonomisk analyse Copyright INEOS 2006
Tørre tall I/O omfang. DCS standard I/O 1913 DCS Foundation Fieldbus 218 DCS Profibus 923 FSC standard I/O 1036 Foundiation Fieldbus Instruments Magnetic Flowmeter ABB (F&P) Coriolis Emerson MVD 2700 Pressure Transmitter Emerson 3051 Vortex Emerson 8800C Radar Vega Vegapuls 63 Emerson 5402 Positioner Samson 3730-5 Temp. transmitter PR 5350A Emerson 644H Copyright INEOS 2006
Riktige valg = Kunnskap Copyright INEOS 2006
Designkriterier og begrensninger 2 sekunders syklus tid for hvert FF segment. Maksimum 16 adresser pr. segment men FIM modul i Honeywell benytter 1 adresse og 1 adresse ønskes reservert til FF terminal. Så maksimum 14 instrumenter pr segment. Dubblerte feltbus kort i Honeywell for å støtte On-line Release endring. Hvert kort har 2 FF segmenter. Hvert instruments eksekveringstid bør ikke overstige 50 msek. Total syklus tid vil da være under 1 sekund for alle instrumenter og det vil være kapasitet til annen kommunikasjon på bussen. Ingen Control On Wire Copyright INEOS 2006
Designkriterier Benyttet Pepperl & Fuchs powermodul og feltbokser. Dette ga oss ingen begrensinger vedrørende strøm og spenningsfall i hvert FF segment. I tillegg fikk vi kortslutnings-sikre spurs. EExi signaler ble også benyttet da ligger Ex-skille ute i EExe feltboks (Pepperl & Fuchs). Copyright INEOS 2006
Muligheter eller begrensninger Copyright INEOS 2006
FASE 1 Engineering Færre tegninger Raskere engineering Fleksible / intelligente instrumenter Reduksjon i komponenter Enklere programmering FASE 2 Installasjon / Igangsettelse Mindre hardware (kabler,barrierer,kabinetter) Felles programmeringsspråk for instrumenter og kontrollere Plassbesparende Felles hardware platform for alle leverandører FASE 3 Drift Tilgang til alle instrument parametere fra DCS systemet Forutsigbart vedlikehold Prosess diagnostikk Bedre nøyaktighet Ingen drifting i prosessverdien Nye instrumenter koples på samme kabel som eksisterende instrumenter Copyright INEOS 2006
Prosesskontroll FF H1 DCS RTP FF IO -MODUL H1 4-20 ma Sikkerhet DCS IO-MODUL IO-MODUL X-wiring Junction -box Junction -box Copyright INEOS 2006
BUS WITH SPURS FF IO MODUL HOST SYSTEM DAISY-CHAIN THREE POINT TO POINT Copyright INEOS 2006
Server Operator Station Network FF H1 Controllere FF H1 FF H1 FF H1 Copyright INEOS 2006
Engineering Workstation / Server Standard funksjonsblokker TT VENT H1 Kontroller TREND ALARM Analog input Analog Output Bias Control Selector Discrete input Discrete output Manual Loader Proportional/Derivat Prop/Int/Der Ratio AI AO B CS DI DO ML PD PID RAT AI PID AO Logikk basert på Fieldbus Foundation standard blir lagt ut i instrumentene I tillegg kommer det 19 funksjonsblokker for avansert Kontroll Copyright INEOS 2006
Engineering work station/server Device Description files Konfigurasjon Instrumenter på H1 nettverket konfigureres ved hjelp av DD filer fra leverandøren. DD filer er en del av FF standarden Host systemer som støtter FF vil kunne lese DD filer. Funksjonalitet i instrumenter og kontrollere er åpen for alle leverandører T FF H1 T Copyright INEOS 2006
EXPERION PKS - Programvare Copyright INEOS 2006
Våre erfaringer Stor forskjell på instrument leverandører Manglende kompetanse på helhetlige løsninger Kompetansekrevende for egen org. (mister noen i en overgangsfase) Krever planlegging og struktur (alarmer, jording, støy, info etc) Reservehold blir et eget kapittel. (Hardware må matche drivere) Copyright INEOS 2006
Våre Problemer Ved lasting av moduler mistes av og til kobling mellom FF-modul og DACA-block Noen instrumenter hopper av buss stadig Støyproblemer Drivere til instrumenter For høy terskel Treg kommunikasjon med feltbuss terminal Noen type instrumenter er vanskelige Copyright INEOS 2006
Våre Problemer Ved lasting av moduler mistes av og til kobling mellom FF-modul og DACA-block Copyright INEOS 2006
Våre Problemer Noen instrumenter hopper av buss stadig X X PT TT FT PT TT LT PT Local X Copyright INEOS 2006
Våre Problemer Reservedeler og Vedlikehold Engineering work station/server Device Description files Så vårt ønske: Når vi bestiller ny FF-Device mottar vi også en DD-fil. Denne legger vi inn på serveren samme dag som vi legger FF-device på lager. Så kommer dagen for enten å bytte en Device eller legge til en ny. Ny Device kobles på bussen, vet selvfølgelig hvilken DD-fil den vil ha og simsalabim Ferdig. T FF H1 T Copyright INEOS 2006
Status nå Ingen problemer Benytter testsystem for å opprettholde kompetanse Copyright INEOS 2006
Våre visjoner Alarmer Standard i kontrollrom Overbroinger Informasjon Copyright INEOS 2006
Spørsmål Jan.gronlid@Ineos.com Takk for meg Copyright INEOS 2006