Produktdatablad Karakteristikk RE88867305 (41 726 84) Tidsrelé plugg multi 24-240V Alternativer Elektrisk tilkobling Kontaktmateriale [In] merkestrøm [Us] matespenning Voltage range Kapslingsmateriale Hovedkarakteristikk Produktspekter Produkt eller komponent type Digitale utganger Zelio Time Universal timing relay Relé Kontakttype og sammensetning 2 C/O Bredde pitch dimensjon Type komponent Tidsforsinker type Tidsforsinkingsområde Plug-in sub-base 11 pin(s) AgNi (cadmium free) 8 A 24 V DC 24...240 V AC på 50/60 Hz 0.85...1.1 Us Self-extinguishing Nøyktighet +/- 0.5 % i samsvar med IEC 61812-1 Temperature drift Voltage drift +/- 0.05 %/ C +/- 0.2 %/V 35 mm RE88867 A AC At B C D Di H Ht W 0.1...1 s 1...10 t 1...10 min 1...10 s 10...100 t 6...60 min 6...60 s Setting accuracy of time delay +/- 10 % of full scale på 25 C i samsvar med IEC 61812-1 Minimum varighet på puls Tilbakestillingstid "on-load" -faktor 100 % Strømforbruk i VA Strømforbruk i W Bryteevne Bryteevne Minimum brytestrøm Maks strøm Maksimum brytespenning Elektrisk levetid Mekanisk levetid 100 ms under load 30 ms 100 ms on de-energisation 32 VA 240 V 0.6 W 24 V 1.5 W 240 V 2000 VA 80 W 10 ma 8 A 250 V 100000 sykluser 8 A på 250 V ohmsk 5000000 sykluser [Uimp] Nominell impulsspenning 5 kv for 1.2...50 µs i samsvar med IEC 60664-1 5 kv for 1.2...50 µs i samsvar med IEC 61812-1 Merking Creepage distance 4 kv/3 i samsvar med IEC 60664-1 CE  informasjonen i denne dokumentasjonen inneholder generelle beskrivelser og / eller tekniske egenskaper ved ytelsen til produktene heri. Denne dokumentasjonen er ikke tenkt som en erstatning for, og skal ikke brukes til avgjørelse for egnethet eller pålitelighet av disse produktene til spesifikke brukerapplikasjoner. Det er brukers eller integrators plikt til å foreta den nødvendige og fullstendige risikoanalyse, evaluering og utprøving av produkter med hensyn til den relevante spesifikke anvendelse eller bruk. Hverken Schneider Electric Industries SAS, eller noen av de tilknyttede selskaper eller datterselskaper er ansvarlig for, eller hefter for misbruk av inneværende opplysninger. 1 / 6
Motstand mot spenningsvariasjon 1 kv (differential mode) i samsvar med IEC 61000-4-5 nivå 3 2 kv (felles modul) i samsvar med IEC 61000-4-5 nivå 3 Lokal varsling Vekt LED indikasjon grønn flashing: timing in progress LED indikasjon grønn on steady: relay energised, no timing in progress LED indikasjon grønn pulsing: relay energised, no timing in progress (except functions Di-D) 0.08 kg Miljø immunity to microbreaks > 10 ms dielektrisk styrke 2.5 kv 1 ma/1 minute 50 Hz i samsvar med IEC 61812-1 standarder produktsertifikater 73/23/EEC 89/336/EEC 93/68/EEC EN 50081-1/2 EN 50082-1/2 IEC 60669-2-3 IEC 61812-1 CSA CURus GL omgivelsestemperatur drift -20...60 C omgivelsestemperatur for lagring -30...60 C IP-grad IP20 (tilkoplingsblokk) i samsvar med IEC 60529 IP40 (kapsling) i samsvar med IEC 60529 IP50 (front panel) i samsvar med IEC 60529 Vibrasjonsmotstand 0,35 mm (f = 10...55 Hz) i samsvar med IEC 60068-2-6 relativ fuktighet 93 % uten kondens i samsvar med IEC 60068-2-3 motstand mot elektrostatisk utladning 6 kv (in contact) i samsvar med IEC 61000-4-2 nivå 3 8 kv (in air) i samsvar med IEC 61000-4-2 nivå 3 motstand mot elektromagnetiske felt 10 V/m, 80 MHz to 1 GHz i samsvar med ENV 50140/204 level 3 10 V/m, 80 MHz to 1 GHz i samsvar med IEC 61000-4-3 level 3 motstand mot raske transienter 1 kv, capacitive connecting clip i samsvar med IEC 61000-4-4 nivå 3 2 kv, direkte i samsvar med IEC 61000-4-4 nivå 3 immunity to radioelectric fields 10 V (0.15...80 MHz) i samsvar med ENV 50141 (IEC 61000-4-6) immunity to voltage dips 60 %/100 ms i samsvar med IEC 61000-4-11 95 %/5 s i samsvar med IEC 61000-4-11 30 %/10 ms i samsvar med IEC 61000-4-11 disturbance radiated/conducted Klasse B i samsvar med EN 55022 (EN 55011 group 1) Width 35 mm Wiring Diagram 2 / 6
Function A : Power on Delay Relay The timing period T begins on energisation. After timing, the output(s) R close(s). The second output can be either timed or instantaneous. Function Ac : On- and Off-Delay Relay with Control Signal After power-up, closing of the control contact C causes the timing period T to start (timing can be interrupted by operating the Gate control contact G). At the end of this timing period, the relay closes. When control contact C re-opens, the timing T starts. At the end of this timing period T, the output reverts to its initial position (timing can be interrupted by operating the Gate control contact G). The second output can be either timed or instantaneous. Function At : Power on Delay Relay (Summation) with Control Signal After power-up, the first opening of control contact C starts the timing. Timing can be interrupted each time control contact closes. When the cumulative total of time periods elapsed reaches the pre-set value T, the output relay closes. T = t1 + t2 +... Function B : Interval Relay with Control Signal 3 / 6
After power-up, pulsing or maintaining control contact C starts the timing T. The output R closes for the duration of the timing period T then reverts to its initial state. Function Bw : Double Interval Relay with Control Signal On closing and opening of control contact C, the output R closes for the duration of the timing period T. Function C : Off-Delay Relay with Control Signal After power-up and closing of the control contact C, the output R closes. When control contact C re-opens, timing T starts. At the end of the timing period, the output(s) R revert(s) to its/their initial state. The second output can be either timed or instantaneous. Function D : Symmetrical Flasher Relay (Starting Pulse Off) Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T. The second output can be either timed or instantaneous. 4 / 6
Function Di : Symmetrical Flasher Relay (Starting Pulse On) Repetitive cycle with two timing periods T of equal duration, with output(s) R changing state at the end of each timing period T. The second output can be either timed or instantaneous. Function H : Interval Relay On energisation of the relay, timing period T starts and the output(s) R close(s). At the end of the timing period T, the output(s) R revert (s) to its/their initial state. The second output can be either timed or instantaneous. Function Ht : Interval Relay (Summation) with Control Signal On energisation, the output R closes for the duration of a timing period T then reverts to its initial state. Pulsing or maintaining control contact C will again close the output R. Timing T is only active when control contact C is released and so the output R will not revert to its initial state until after a time t1 + t2 +... The relay memorises the total, cumulative opening time of control contact C and, once the set time T is reached, the output R reverts to its initial state. T = t1 + t2 +... Legend Relay de-energised Relay energised Output open Output closed 5 / 6
C G R Control contact Gate Relay or solid state output R1/R22 timed outputs R2 The second output is instantaneous if the right position is selected inst. T Timing period Ta - Adjustable On-delay Tr - Adjustable Off-delay U Supply 6 / 6